NYIFY-F (300/500 V)
CONSTRUCTION
Conductor
Fine-stranded copper (Class 5)
Insulation
Polyvinyl chloride
Outer Sheath
Polyvinyl chloride
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Lead free
APPLICATIONS
Suitable for dry and humid areas. All type of factory, warehouse and depots where there is fire and explosion threat. Not suitable for underground. Used in fixed installations laying in conduit on and under plaster.
TECHNICAL DATA ( Cu/PVC/PVC )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
---|---|---|---|---|
Air (A) | ||||
NYIFY-F (300/500 V)
|
||||
2x1 | 4.0 x 9.3 | 56 | 19.5 | 13 |
2x1.5 | 4.4 x 10.6 | 77 | 13.3 | 16 |
2x2.5 | 5.0 x 12.0 | 106 | 7.98 | 21 |
2x4 | 5.6 x 14.1 | 142 | 4.95 | 27 |
3x1 | 4.0 x 14.9 | 84 | 19.5 | 13 |
3x1.5 | 4.9 x 17.6 | 108 | 13.3 | 16 |
3x2.5 | 5.0 x 19.6 | 148 | 7.98 | 21 |
3x4 | 5.6 x 23.1 | 199 | 4.95 | 27 |