(NVV) NYM
05VV-U / 05VV-R (300/500 V)
CONSTRUCTION
Conductor
Solid ond stranded copper (Class 2)
Insulation
Polyvinyl chloride
Filler
Polyvinyl chloride
Outer Sheath
Polyvinyl chloride
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Lead free
APPLICATIONS
Used in dry humid areas that there are no mechanical compulsion, under and on the plaster.
TECHNICAL DATA ( Cu/PVC/PVC )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
---|---|---|---|---|
Air (A) | ||||
(NVV) NYM / H05VV-U, H05VV-R (300/500 V)
|
||||
2x1.5 | 8.8 | 121 | 12.1 | 22 |
2x2.5 | 10.0 | 163 | 7.41 | 30 |
2x4 | 10.9 | 212 | 4.61 | 40 |
2x6 | 11.8 | 270 | 3.08 | 51 |
2x10 | 15.7 | 498 | 1.83 | 70 |
2x16 | 18.4 | 698 | 1.15 | 94 |
2x25 | 20.8 | 1001 | 0.727 | 119 |
2x35 | 23.4 | 1320 | 0.524 | 148 |
3x1.5 | 8.9 | 134 | 12.1 | 16.5 |
3x2.5 | 10.5 | 194 | 7.41 | 23 |
3x4 | 11.4 | 254 | 4.61 | 30 |
3x6 | 12.9 | 343 | 3.08 | 38 |
3x10 | 16.4 | 605 | 1.83 | 52 |
3x16 | 18.7 | 858 | 1.15 | 69 |
3x25 | 22.2 | 1156 | 0.727 | 90 |
3x35 | 24.5 | 1500 | 0.524 | 111 |
4x1.5 | 9.9 | 168 | 12.1 | 16.5 |
4x2.5 | 11.3 | 233 | 7.41 | 23 |
4x4 | 10.3 | 333 | 4.61 | 30 |
4x6 | 14.2 | 430 | 3.08 | 38 |
4x10 | 18.2 | 770 | 1.83 | 52 |
4x16 | 20.9 | 1106 | 1.15 | 69 |
5x10 | 19.2 | 820 | 1.83 | 60 |
5x16 | 21.9 | 1170 | 1.15 | 80 |