Skip links

YDYp

(300/500 V & 450/750 v)

YDYp

PVC Insulated, Low Voltage Power Cables

CONSTRUCTION

Conductor

Som bakır
Solid copper (Class 1)

Insulation

Polyvinyl chloride

Outer Sheath

PVC
Polyvinyl chloride

SPECIFICATIONS

Max. short circuit temperature
Max. operating temperature
-40 derece
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
2-kv
AC test voltage
300/500-v
Rated voltage Uo/U
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
ROHS & REACH compliant
Lead free

APPLICATIONS

Installation in walls, on boards and in channels or embedded in plaster.

TECHNICAL DATA ( Cu/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YVV-U (NYY), YVV-R (NYY) (0.6/1 kV)
1x4 7.01 87 4.61 59 50
1x6 7.51 109 3.08 73 62
1x10 8.65 158 1.83 97 83
1x16 9.60 219 1.15 125 107
1x25 11.00 319 0.727 161 138
1x35 12.10 417 0.524 192 164
1x50 13.80 556 0.387 227 195
1x70 15.30 761 0.268 278 238
1x95 17.60 1033 0.193 332 286
1x120 19.50 1287 0.153 377 325
1x150 21.00 1563 0.124 423 365