YVV (NYY FLEX) (0,6/1 KV)
CONSTRUCTION
Conductor
Fine-stranded copper (Class 5)
Insulation
Polyvinyl chloride
Outer Sheath
Polyvinyl chloride
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Lead free
APPLICATIONS
Used in underground which there not much outer factors and inside cable conduits.
TECHNICAL DATA ( CU/PVC/PVC )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in | |||
---|---|---|---|---|---|---|---|
Ground (A) | Air (A) | ||||||
YVV (NYY FLEX) (0,6/1 kV)
|
|||||||
1x4 | 8,2 | 100 | 4,95 | 59 | 50 | 45 | 33 |
1x6 | 8,5 | 120 | 3,30 | 73 | 62 | 59 | 43 |
1x10 | 9,2 | 180 | 1,91 | 97 | 83 | 81 | 60 |
1x16 | 10,2 | 235 | 1,21 | 125 | 107 | 110 | 82 |
1x25 | 11,6 | 345 | 0,780 | 161 | 138 | 146 | 110 |
1x35 | 13,1 | 445 | 0,554 | 192 | 164 | 181 | 137 |
1x50 | 14,4 | 600 | 0,386 | 227 | 195 | 219 | 167 |
1x70 | 16,3 | 785 | 0,272 | 278 | 238 | 281 | 216 |
1x95 | 18,2 | 1050 | 0,206 | 332 | 286 | 341 | 264 |
1x120 | 20,5 | 1300 | 0,161 | 377 | 325 | 396 | 308 |
1x150 | 22,1 | 1570 | 0,129 | 423 | 365 | 456 | 356 |