Skip links

YVV (NYY FLEX) (0,6/1 KV)

YVV 2

PVC Insulated, Low Voltage Power Cables

TS IEC 60502-1

CONSTRUCTION

Conductor

İnce çok telli bakır
Fine-stranded copper (Class 5)

Insulation

Polyvinyl chloride

Filler

PVC
Polyvinyl chloride

Outer Sheath

PVC 4
Polyvinyl chloride

SPECIFICATIONS

Max. short circuit temperature
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları
Uygulama alanları

Used in underground which there not much outer factors and inside cable conduits.

TECHNICAL DATA ( CU/PVC/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YVV (NYY FLEX) (0.6/1 kV)
2x6 12.2 250 3.30 68 51
2x10 15.8 424 1.91 90 70
2x16 18.0 588 1.21 116 94
2x25 23.7 1019 0.780 150 119
2x35 25.7 1269 0.554 181 148
2x50 30.1 1777 0.386 118 153
2x70 33.7 2302 0.272 149 196
3x6 13.0 305 3.30 59 43
3x10 16.8 515 1.91 79 59
3x16 20.7 851 1.21 102 79
3x25 24.4 1221 0.780 133 106
3x35 27.1 1602 0.554 159 129
3x50 31.4 2210 0.386 188 157
3x70 35.2 2909 0.272 232 199
3x95 41.2 3932 0.206 280 246
3x120 43.6 4733 0.161 318 285
3x16+10 21.9 981 1.21/1.91 102 79
3x25+16 25.8 1421 0.780/1.21 133 106
3x35+16 28.1 1757 0.554/1.21 159 129
3x50+25 32.8 2493 0.386/0.780 188 157
3x70+35 36.8 3295 0.272/0.554 232 199
3x95+50 42.5 4396 0.206/0.386 280 246
3x120+70 46.2 5489 0.161/0.272 318 285