YVV (NYY FLEX) (0,6/1 KV)
CONSTRUCTION
Conductor
Fine-stranded copper (Class 5)
Insulation
Polyvinyl chloride
Filler
Polyvinyl chloride
Outer Sheath
Polyvinyl chloride
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Lead free
APPLICATIONS
Used in underground which there not much outer factors and inside cable conduits.
TECHNICAL DATA ( CU/PVC/PVC/PVC )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in | |
---|---|---|---|---|---|
Ground (A) | Air (A) | ||||
YVV (NYY FLEX) (0.6/1 kV)
|
|||||
4x6 | 15.8 | 423 | 3.30 | 59 | 43 |
4x10 | 20.0 | 764 | 1.91 | 79 | 60 |
4x16 | 22.5 | 1047 | 1.21 | 102 | 80 |
4x24 | 26.8 | 1526 | 0.780 | 133 | 101 |
4x35 | 30.1 | 2038 | 0.554 | 159 | 126 |
4x50 | 34.8 | 2801 | 0.386 | 188 | 153 |
4x70 | 39.2 | 3717 | 0.272 | 232 | 199 |
4x95 | 45.4 | 4967 | 0.206 | 280 | 246 |
5x4 | 16.0 | 469 | 4.95 | 47 | 34 |
5x6 | 17.0 | 597 | 4.30 | 59 | 43 |
5x10 | 20.6 | 890 | 1.91 | 79 | 60 |
5x16 | 25.2 | 1317 | 1.21 | 102 | 80 |
5x25 | 29.9 | 1909 | 0.780 | 133 | 101 |
5x35 | 33.0 | 2491 | 0.554 | 159 | 126 |
5x50 | 38.9 | 3542 | 0.386 | 188 | 153 |
5x70 | 44.9 | 4782 | 0.272 | 232 | 199 |
5x95 | 50.8 | 6602 | 0.206 | 280 | 246 |