YXV (N2XY) (0,6/1 kV)

YXV 4

XLPE Insulated, Multi-core Cables With Copper Conductor

TS IEC 60502-1

CONSTRUCTION

Conductor

Som veya örgülü bakır
Solid or stranded copper (Class 1 or Class 2)

Insulation

XLPE
Cross linkable polyethylene

Outer Sheath

PVC
Polyvinyl chloride

Outer Sheath

PVC 4
Polyvinyl chloride

SPECIFICATIONS

250 derece
Max. short circuit temperature
90 derece
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları

This cable having very low dilectric loss is used indoor, in cable ducts and in industrial plants or switching stations where mechanical damage is not anticipated. Suitable for comparatively high ambient temperature due to high maximum permissible conductor temperature.

TECHNICAL DATA ( Cu/XLPE/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YXV (N2XY) (0,6/1 kV)
4x16/10 22,3 1099 1,15/1,83 112 98
4x25/16 25,8 1597 0,727/1,15 145 133
4x35/16 28,4 2016 0,524/1,15 174 162
4x50/25 32,5 2717 0,387/0,727 206 197
4x70/35 36,8 3735 0,268/0,524 254 250
4x95/50 41,7 5011 0,193/0,387 305 308
5x1,5 12,3 230 12,1 31 24
5x2,5 13,4 296 7,41 40 32
5x4 14,6 396 4,61 52 42
5x6 15,9 512 3,08 64 53
5x10 18,3 748 1,83 86 74
5x16 21,8 1125 1,15 112 98
5x25 25,8 1682 0,727 145 133
5x35 28,9 2236 0,524 174 162
5x50 33,6 3035 0,387 206 197
5x70 38,6 4248 0,268 254 250