YAVV-NAVY (0,6/1 kV)

YAVV-NAYY

PVC Insulated, Low Voltage Power Cables With Aluminium Conductor

TS IEC 60502-1

CONSTRUCTION

Conductor

Aluminyum
Stranded aluminium (Class 2)

Insulation

Polyvinyl chloride

Outer Sheath

PVC
Polyvinyl chloride

SPECIFICATIONS

Max. short circuit temperature
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
Max. short circuit temperature
06/1 kv
Max. operating temperature NBR Used as a welding cable
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları

Used as illumination cable in energy networks that there are not much mechanical compulsion in the exterior, underground, in cable trays and watering foundations.

TECHNICAL DATA (AL/PVC/PVC)

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YAVV / NAYY (0,6/1 kV)
1x16 9,3 120 1,910 - - - -
1x25 11,5 174 1,200 125 105 87 75
1x35 12,7 213 0,868 150 127 131 113
1x50 14,6 277 0,641 173 151 160 138
1x70 16,1 355 0,443 211 186 202 174
1x95 18,7 476 0,320 261 223 249 210
1x120 20,4 568 0,253 297 254 291 244
1x150 22,5 697 0,206 333 285 333 281