AER-ABC ALPEK (0,6/1 kV)
CONSTRUCTION
Conductor
Stranded aluminium (Class 2)
Insulation
PE or XLPE
Outer Sheath
Alloy aluminium
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
Max. short circuit temperature
Max. operating temperature NBR
Used as a welding cable
ROHS & REACH compliant
Lead free
APPLICATIONS
Aerial cables used power distribution in populated areas.
TECHNICAL DATA ( AL/PVC(PE) )
Nominal Cross Section mm² | Diameter of Messenger mm | Diameter of Conductor mm | Conductor DC Resistance max. ohm/km (20°C) | Resistance max. ohm/km (20°C) | Net Weight kg/km approximately |
---|---|---|---|---|---|
AER-ABC / ALPEK (0.6/1 kV) | |||||
1x16+25 | 5.9 | 4.5 | 1.91 | 1.38 | 140 |
1x25+35 | 6.9 | 6.2 | 1.20 | 0.986 | 200 |
1x35+50 | 8.1 | 7.1 | 0.868 | 0.72 | 280 |
1x16+1x16+25 | 5.9 | 4.5 | 1.91 | 1.38 | 210 |
3x16+25 | 5.9 | 4.5 | 1.91 | 1.38 | 280 |
3x25+35 | 6.9 | 6.3 | 1.20 | 0.986 | 400 |
3x35+50 | 8.1 | 7.2 | 0.868 | 0.72 | 560 |
3x50+70 | 9.7 | 8.1 | 0.641 | 0.493 | 730 |
3x70+95 | 11.4 | 9.8 | 0.443 | 0.363 | 1030 |
3x120+95 | 11 | 12.6 | 0.253 | 0.363 | 1150 |
3x16+1x16+25 | 5.9 | 4.5 | 1.91 | 1.38 | 350 |
3x25+1x16+35 | 6.9 | 6.3 | 1.20/1.91 | 0.986 | 480 |
3x35+1x16+50 | 8.1 | 7.2 | 0.868/1.91 | 0.72 | 630 |
3x50+1x16+70 | 9.7 | 8.1 | 0.641/1.91 | 0.493 | 800 |
3x70+1x16+95 | 11.4 | 9.8 | 0.443/1.91 | 0.363 | 1100 |
4x16+25 | 5.9 | 4.5 | 1.91 | 1.38 | 350 |
4x25+35 | 6.9 | 6.1 | 1.20 | 0.986 | 510 |