Skip links

H05V-U (300/500 V)

H07V-U (450/750 V)

PVC Insulated, Non-Sheathed Single Core Cables

TS EN 50525-2-31

CONSTRUCTION

Conductor

Som veya örgülü bakır
Solid copper (Class 1)

Insulation

Polyvinyl chloride

SPECIFICATIONS

Max. short circuit temperature
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Used in closed and dry areas, switch and distribution boards, fixed installations laying in conduit on and under plaster.

TECHNICAL DATA ( CU/PVC )

Nominal Cross Section  mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°) max. ohm/km Current Carrying Capacity in
Condouit  (A) Air (A)
H05V-U (300/500 V)
0,5 2,0 9 36 - -
0,75 2,2 12 24,5 - 16
1 2,4 13 18,1 11 19
H07V-U (450/750 V)
1,5 2,7 21 12,1 14,5 24
2,5 3,2 34 7,41 19,5 32
4 3,7 50 4,61 26 42
6 4,2 71 3,08 34 54
10 5,4 116 1,83 46 73