H07V-R (450/750V)
CONSTRUCTION
Conductor
Stranded copper (Class2)
Insulation
Polyvinyl chloride
SPECIFICATION
Max. short circuit temperature
Max. operating temperature
Min. bending radius
if D<8 then 4xD
if 8<D<12 then 5xD
if D>12 then 6xD
if 8<D<12 then 5xD
if D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Lead free
APPLICATIONS
Used in closed and dry areas, switch and distribution boards, fixed installations laying in conduit on and under plaster.
TECHNICAL DATA ( CU/PVC )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°) max. ohm/km | Current Carrying Capacity in | |
---|---|---|---|---|---|
Condouit (A) | Air (A) | ||||
H07V-R (450/750 V)
|
|||||
1,5 | 3,0 | 21 | 12,1 | 14,5 | 24 |
2,5 | 3,6 | 32 | 7,41 | 19,5 | 32 |
4 | 4,2 | 48 | 4,61 | 26 | 42 |
6 | 4,8 | 67 | 3,08 | 34 | 54 |
10 | 5,9 | 110 | 1,83 | 46 | 73 |
16 | 6,9 | 181 | 1,15 | 61 | 98 |
25 | 8,2 | 280 | 0,727 | 80 | 129 |
35 | 9,3 | 382 | 0,524 | 99 | 158 |
50 | 10,8 | 542 | 0,387 | 119 | 198 |
70 | 12,4 | 745 | 0,268 | 151 | 245 |
95 | 14,5 | 1010 | 0,193 | 182 | 292 |
120 | 15,9 | 1260 | 0,153 | 210 | 344 |
150 | 17,7 | 1575 | 0,124 | 240 | 391 |