H05Z1-K (300/500 V)
H07Z1-K (450/750 V)
CONSTRUCTION
Conductor
Fine-stranded copper (Class 5)
Insulation
Low smoke zero halogen cross linkable
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Halogen free
EN 50525-1 - EN 50267
Low smoke - EN 61034
APPLICATIONS
Installation in surface mounted or embedded conduits or similar closed systems. Low level of smoke emission and corrosive gases in case of fire.
TECHNICAL DATA ( CU/XL-LSZH )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°) max. ohm/km | Current Carrying Capacity in | |
---|---|---|---|---|---|
Condouit (A) | Air (A) | ||||
H05Z1-K (300/500 V)
|
|||||
0,5 | 2,1 | 9 | 39 | - | 12 |
0,75 | 2,3 | 12 | 26 | - | 15 |
1 | 2,5 | 13 | 19,5 | 11 | 19 |
H07Z1-K (450/750 V) | |||||
1,5 | 3,0 | 19 | 13,3 | 14,5 | 24 |
2,5 | 3,7 | 30 | 7,98 | 19,5 | 32 |
4 | 4,5 | 44 | 4,95 | 26 | 42 |
6 | 5,5 | 61 | 3,30 | 34 | 54 |
10 | 6,5 | 105 | 1,91 | 46 | 73 |
16 | 7,5 | 158 | 1,21 | 61 | 98 |
25 | 10,0 | 253 | 0,780 | 80 | 129 |
35 | 11,0 | 345 | 0,554 | 99 | 158 |
50 | 13,0 | 495 | 0,386 | 119 | 198 |
70 | 15,0 | 670 | 0,272 | 151 | 245 |
95 | 17,0 | 905 | 0,206 | 182 | 292 |
120 | 19,0 | 1132 | 0,161 | 210 | 344 |
150 | 21,0 | 1415 | 0,129 | 240 | 391 |