FLAT TWIN (300/500 V)

Flat Twin

PVC Insulated, PVC Sheathed Flat Cables

CONSTRUCTION

Conductor

Som veya örgülü bakır
Solid or stranded copper (Class 1 or Class 2)

Insulation

Polyvinyl chloride

Outer Sheath

PVC
Polyvinyl chloride

SPECIFICATIONS

Max. short circuit temperature
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
2-kv
AC test voltage
300/500-v
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Used as surface wiring where there is little mechanical damage risk, or in conduit.

TECHNICAL DATA ( CU/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Lower Limit Upper Limit Air (A)
BS 6004 FLAT TWIN (300/500 V)
2x1re 3,9x6,1 4,8x7,4 60 18,1 13
2x1,5re 4,4x7,0 5,3x8,5 75 12,1 16
2x1,5rm 4,5x7,2 5,4x8,7 76 12,1 16
2x2,5re 5,1x8,4 6,2x10,1 112 7,41 21
2x2,5rm 5,2x8,5 6,3x10,3 113 7,41 21
2x4rm 5,7x9,5 6,9x11,5 154 4,61 27
2x6rm 6,4x10,8 7,8x13,0 203 3,08 34
2x10rm 7,9x13,4 9,5x16,2 315 1,83 45
2x16rm 8,9x15,4 10,8x18,6 448 1,15 57
3x1re 3,9x8,4 4,8x10,1 85 18,1 13
3x1,5re 4,4x9,6 5,3x11,7 106 12,1 16
3x2,5re 5,1x11,6 6,2x14,0 159 7,41 21
3x4rm 5,9x13,5 7,1x16,3 222 4,61 27
3x6rm 6,4x15,1 7,8x18,2 293 3,08 34
3x10rm 7,9x19,0 9,5x13,0 457 1,83 45
3x16rm 8,9x21,8 10,8x26,3 654 1,15 57