H05V-U (300/500 V)
H07V-U (450/750 V)
CONSTRUCTION
Conductor
Solid copper (Class 1)
Insulation
Polyvinyl chloride
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Lead free
APPLICATIONS
Used in closed and dry areas, switch and distribution boards, fixed installations laying in conduit on and under plaster.
TECHNICAL DATA ( CU/PVC )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°) max. ohm/km | Current Carrying Capacity in | |
---|---|---|---|---|---|
Condouit (A) | Air (A) | ||||
H05V-U (300/500 V)
|
|||||
0,5 | 2,0 | 9 | 36 | - | - |
0,75 | 2,2 | 12 | 24,5 | - | 16 |
1 | 2,4 | 13 | 18,1 | 11 | 19 |
H07V-U (450/750 V) | |||||
1,5 | 2,7 | 21 | 12,1 | 14,5 | 24 |
2,5 | 3,2 | 34 | 7,41 | 19,5 | 32 |
4 | 3,7 | 50 | 4,61 | 26 | 42 |
6 | 4,2 | 71 | 3,08 | 34 | 54 |
10 | 5,4 | 116 | 1,83 | 46 | 73 |