Skip links

H07V-R (450/750V)

PVC Insulated, Single Core Cables

TS EN 50525-2-31

CONSTRUCTION

Conductor

Stranded copper (Class2)

Insulation

Polyvinyl chloride

SPECIFICATION

Max. short circuit temperature
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
if D<8 then 4xD
if 8<D<12 then 5xD
if D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
2.5 KV
AC test voltage
450/750V
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Used in closed and dry areas, switch and distribution boards, fixed installations laying in conduit on and under plaster.

TECHNICAL DATA ( CU/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°) max. ohm/km Current Carrying Capacity in
Condouit  (A) Air (A)
H07V-R (450/750 V)
1,5 3,0 21 12,1 14,5 24
2,5 3,6 32 7,41 19,5 32
4 4,2 48 4,61 26 42
6 4,8 67 3,08 34 54
10 5,9 110 1,83 46 73
16 6,9 181 1,15 61 98
25 8,2 280 0,727 80 129
35 9,3 382 0,524 99 158
50 10,8 542 0,387 119 198
70 12,4 745 0,268 151 245
95 14,5 1010 0,193 182 292
120 15,9 1260 0,153 210 344
150 17,7 1575 0,124 240 391