H07Z1-R (450/470V)
CONSTRUCTION
Conductor
Solid or stranded coppper (Class 1 or Class 2)
Insulation
Low smoke zero halogen
SPECIFICATION
Max. short circuit temperature
Max. operating temperature
Min. bending radius
if D<8 then 4xD
if 8<D<12 then 5xD
if D>12 then 6xD
if 8<D<12 then 5xD
if D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
Halogen free
EN 50525-1 EN 50267
Low smoke - EN 61034
ROHS & REACH compliant
APPLICATIONS
HALOGEN FREE, FLAME RETARDANT, HEAT RESISTANT, SINGLE CORE CABLES
TECHNICAL DATA ( CU/PVC )
Nomnal Cross Secton mm2
|
Overall Dameter mm approxmately
|
Net Weght kg/km approxmately
|
Conductor DC Resstance at (20°C) max. ohm/km
|
Current Carryng Capacty
|
|
---|---|---|---|---|---|
Condut (A)
|
Air (A)
|
||||
H07Z1-R (450/750 V)
|
|||||
1,5 | 3,0 | 24 | 12,1 | 14,5 | 24 |
2,5 | 3,6 | 32 | 7,41 | 19,5 | 32 |
4 | 4,0 | 42 | 4,61 | 26 | 42 |
6 | 4,8 | 54 | 3,08 | 34 | 54 |
10 | 5,9 | 73 | 1,83 | 46 | 73 |
16 | 6,6 | 98 | 1,15 | 61 | 98 |
25 | 8,4 | 129 | 0,727 | 80 | 129 |
35 | 9,4 | 158 | 0,524 | 99 | 158 |
50 | 10,7 | 198 | 0,387 | 119 | 198 |
70 | 12,6 | 245 | 0,268 | 151 | 245 |
95 | 14,8 | 292 | 0,193 | 182 | 292 |
120 | 16,2 | 344 | 0,153 | 210 | 344 |
150 | 18,0 | 1 | 0,124 | 240 | 391 |