YXV (N2XY) (0,6/1 kV)

N2XY FLEX 2

XLPE Insulated, PVC Sheathed, Flexible, Multi-core Underground Cables

TS IEC 60502-1

CONSTRUCTION

Conductor

İnce Çok Telli Bakir
Fine-stranded copper (Class 5)

Insulation

XLPE
Cross linkable polyethylene

Outer Sheath

PVC
Polyvinyl chloride

SPECIFICATIONS

250 derece
Max. short circuit temperature
90 derece
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları

For indoor and outdoor in cables ducts and in industrial plants or switching stations where mechanical damage is not anticipated. Suitable for comparatively high ambient temperature due to high maximum permissible conductor temperature.

TECHNICAL DATA ( CU/XLPE/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
N2XY FLEX (0.6/1 kV)
2x1.5 9.9 133 13.3 37 26
2x2.5 10.0 166 7.98 49 36
2x4 11.9 216 4.95 64 49
2x6 13.3 283 3.30 79 63
2x10 14.9 403 1.91 106 86
2x16 17.3 579 1.21 137 115
2x25 21.4 893 0.780 176 149
2x35 23.2 1115 0.554 213 185
2x50 26.4 1521 0.386 252 225
2x70 30.6 2070 0.272 254 250
2x95 34.4 2709 0.206 305 308
2x120 38.6 3393 0.161 348 359
2x150 41.6 4035 0.129 392 412
3x1.5 10.4 153 13.3 31 24
3x2.5 11.3 194 7.98 40 32
3x4 12.6 258 4.95 52 42
3x6 14.1 342 3.30 64 53
3x10 15.8 489 1.91 86 74
3x16 18.4 713 1.21 112 98
3x25 22.8 1101 0.780 145 133
3x35 24.7 1395 0.554 174 162
3x50 28.2 1927 0.386 206 197
3x70 32.9 2654 0.272 254 250
3x95 37.0 3490 0.206 305 308
3x120 41.5 4369 0.161 348 359
3x150 47.3 5277 0.129 392 412