NA2XH (0,6/1 kV)
CONSTRUCTION
Conductor
Stranded aluminium (Class 2)
Insulation
Cross linkable polyethylene
Outer Sheath
Halogen free flame retardant
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
Max. short circuit temperature
Max. operating temperature NBR
Used as a welding cable
Halogen free
EN 50525-1 - EN 50267
Low smoke - EN 61034
ROHS & REACH compliant
APPLICATIONS
Used in refineries, hotels, schools, tunnels, high cunstructions, hospitals, power plants, data processing center, populated business centers where there is a risk of fire.
TECHNICAL DATA (AI/XLPE/HFFR)
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in | |||
---|---|---|---|---|---|---|---|
Ground (A) | Air (A) | ||||||
NA2XH (0,6/1 kV)
|
|||||||
1x16 | 8,7 | 106 | 1,91 | - | - | - | - |
1x25 | 10,9 | 153 | 1,20 | - | - | - | - |
1x35 | 12,1 | 195 | 0,868 | 164 | 137 | 163 | 131 |
1x50 | 13,8 | 250 | 0,641 | 195 | 163 | 200 | 161 |
1x70 | 15,5 | 325 | 0,443 | 238 | 201 | 254 | 205 |
1x95 | 17,7 | 434 | 0,320 | 284 | 240 | 313 | 253 |
1x120 | 19,6 | 521 | 0,253 | 325 | 274 | 366 | 296 |
1x150 | 21,7 | 640 | 0,206 | 361 | 308 | 420 | 341 |