NA2XY (0,6/1 kV)
CONSTRUCTION
Conductor
Stranded aluminium (Class 2)
Insulation
Cross linkable polyethylene
Outer Sheath
Polyvinyl chloride
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
Max. short circuit temperature
Max. operating temperature NBR
Used as a welding cable
ROHS & REACH compliant
Lead free
APPLICATIONS
This cable having very low dilectric loss is used indoor, in cable ducts and in industrial plants or switching stations where mechanical damage is not anticipated. Suitable for comparatively high ambient temperature due to high maximum permissible conductor temperature.
TECHNICAL DATA (AL/XLPE/PVC)
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in | |||
---|---|---|---|---|---|---|---|
Ground (A) | Air (A) | ||||||
NA2XY (0,6/1 kV)
|
|||||||
1x16 | 8,7 | 105 | 1,910 | - | - | - | - |
1x25 | 10,9 | 154 | 1,200 | - | - | - | - |
1x35 | 12,1 | 195 | 0,868 | 164 | 137 | 163 | 131 |
1x50 | 13,8 | 250 | 0,641 | 195 | 163 | 200 | 161 |
1x70 | 15,5 | 325 | 0,443 | 238 | 201 | 254 | 205 |
1x95 | 17,7 | 434 | 0,320 | 284 | 240 | 313 | 253 |
1x120 | 19,6 | 521 | 0,253 | 325 | 274 | 366 | 296 |
1x150 | 21,7 | 640 | 0,206 | 361 | 308 | 420 | 341 |