NHMH (300/500 V)
CONSTRUCTION
Conductor
Solid or stranded copper (Class 1 or Class 2)
Insulation
Polypropylene
Filler
Halogen free flame
retardant
Outer Sheath
Halogen free flame
retardant
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
Halogen free
EN 50525-1 - EN 50267
Lead free
ROHS & REACH compliant
APPLICATIONS
Used in refineries, hotels, mines, tunnels, high cunstructions, hospitals, power plants, data processing center, populated business centers where there is a risk of fire.
TECHNICAL DATA ( CU/XPLE/PVC/PVC )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity | |
---|---|---|---|---|---|
Ground (A) | Air (A) | ||||
NMHH (300/500 V)
|
|||||
2x1.5 | 7.9 | 96 | 12.1 | - | 22 |
2x2.5 | 8.7 | 126 | 7.41 | - | 30 |
2x4 | 10.0 | 178 | 4.61 | - | 40 |
2x6 | 11.0 | 231 | 3.08 | - | 51 |
2x10 | 13.8 | 376 | 1.83 | - | 70 |
2x16 | 16.4 | 545 | 1.15 | - | 98 |
3x1.5 | 8.3 | 115 | 12.1 | - | 22 |
3x2.5 | 9.2 | 154 | 7.41 | - | 30 |
3x4 | 10.4 | 222 | 4.61 | - | 40 |
3x6 | 12.0 | 302 | 3.08 | - | 51 |
3x10 | 14.6 | 477 | 1.83 | - | 70 |
3x16 | 17.6 | 709 | 1.15 | - | 98.5 |
4x1.5 | 8.9 | 138 | 12.1 | - | 18.5 |
4x2.5 | 9.9 | 187 | 7.41 | - | 25 |
4x4 | 11.9 | 286 | 4.61 | - | 34 |
4x6 | 13.5 | 390 | 3.08 | - | 43 |
4x10 | 15.8 | 594 | 1.83 | - | 60 |
4x16 | 19.4 | 897 | 1.15 | - | 80 |
5x1.5 | 9.6 | 164 | 12.1 | - | 18.5 |
5x2.5 | 10.7 | 224 | 7.41 | - | 25 |
5x4 | 13.2 | 355 | 4.61 | - | 34 |
5x6 | 14.6 | 470 | 3.08 | - | 43 |
5x10 | 17.2 | 723 | 1.83 | - | 60 |
5x16 | 21.5 | 1111 | 1.15 | - | 80 |