YVV (NYY FLEX) (0,6/1 KV)

YVV (NYY FLEX)

PVC Insulated, Low Voltage Power Cables

TS IEC 60502-1

CONSTRUCTION

Conductor

İnce çok telli bakır
Fine-stranded copper (Class 5)

Insulation

Polyvinyl chloride

Outer Sheath

PVC
Polyvinyl chloride

SPECIFICATIONS

Max. short circuit temperature
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları
Uygulama alanları

Used in underground which there not much outer factors and inside cable conduits.

TECHNICAL DATA ( CU/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YVV (NYY FLEX) (0,6/1 kV)
1x4 8,2 100 4,95 59 50 45 33
1x6 8,5 120 3,30 73 62 59 43
1x10 9,2 180 1,91 97 83 81 60
1x16 10,2 235 1,21 125 107 110 82
1x25 11,6 345 0,780 161 138 146 110
1x35 13,1 445 0,554 192 164 181 137
1x50 14,4 600 0,386 227 195 219 167
1x70 16,3 785 0,272 278 238 281 216
1x95 18,2 1050 0,206 332 286 341 264
1x120 20,5 1300 0,161 377 325 396 308
1x150 22,1 1570 0,129 423 365 456 356