YVV (NYY FLEX) (0,6/1 KV)

YVV 3

PVC Insulated, Low Voltage Power Cables

TS IEC 60502-1

CONSTRUCTION

Conductor

İnce çok telli bakır
Fine-stranded copper (Class 5)

Insulation

Polyvinyl chloride

Filler

PVC
Polyvinyl chloride

Outer Sheath

PVC 4
Polyvinyl chloride

SPECIFICATIONS

Max. short circuit temperature
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları
Uygulama alanları

Used in underground which there not much outer factors and inside cable conduits.

TECHNICAL DATA ( CU/PVC/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YVV (NYY FLEX) (0.6/1 kV)
4x6 15.8 423 3.30 59 43
4x10 20.0 764 1.91 79 60
4x16 22.5 1047 1.21 102 80
4x24 26.8 1526 0.780 133 101
4x35 30.1 2038 0.554 159 126
4x50 34.8 2801 0.386 188 153
4x70 39.2 3717 0.272 232 199
4x95 45.4 4967 0.206 280 246
5x4 16.0 469 4.95 47 34
5x6 17.0 597 4.30 59 43
5x10 20.6 890 1.91 79 60
5x16 25.2 1317 1.21 102 80
5x25 29.9 1909 0.780 133 101
5x35 33.0 2491 0.554 159 126
5x50 38.9 3542 0.386 188 153
5x70 44.9 4782 0.272 232 199
5x95 50.8 6602 0.206 280 246