YVV-R (NYY), YVV-U (NYY) (0,6/1 kV)

YVV-R, YVV-U-2

Pvc Insulated, Low Voltage Power Cables

TS IEC 60502-1

CONSTRUCTION

Conductor

Som veya örgülü bakır
Solid or stranded copper (Class 1 or Class 2)

Insulation

Polyvinyl chloride

Filler

PVC
Polyvinyl chloride

Outer Sheath

PVC 4
Polyvinyl chloride

SPECIFICATIONS

Max. short circuit temperature
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
2-kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları
Uygulama alanları

Used in underground which there not much outer factors and inside cable conduits.

TECHNICAL DATA ( Cu/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YVV-U (NYY), YVV-R (NYY) (0.6/1 kV)
2x1.5 10.54 161 12.1 32 22
2x2.5 11.32 196 7.41 42 30
2x4 13.02 272 4.61 54 40
2x6 14.02 334 3.08 68 51
2x10 16.30 478 1.83 90 70
2x16 18.80 675 1.15 116 94
2x25 21.20 930 0.727 150 119
2x35 23.40 1196 0.524 181 148
3x1.5 10.80 177 12.1 27 19.5
3x2.5 11.90 229 7.41 36 25
3x4 13.70 322 4.61 47 34
3x6 14.80 403 3.08 59 43
3x10 17.50 596 1.83 79 59
3x16 19.50 813 1.15 102 79
3x25 22.60 1177 0.727 133 106
3x35 24.90 1521 0.524 159 129
3x50 28.80 2054 0.387 188 157
3x70 32.30 2792 0.268 232 199
3x95 37.10 3769 0.193 280 246
3x120 41.00 4675 0.153 318 285
3x150 44.50 5676 0.124 359 326