YVV-R (NYY), YVV-U (NYY) (0,6/1 kV)
CONSTRUCTION
Conductor
Solid or stranded copper (Class 1 or Class 2)
Insulation
Polyvinyl chloride
Filler
Polyvinyl chloride
Outer Sheath
Polyvinyl chloride
SPECIFICATIONS
Max. short circuit temperature
Max. operating temperature
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
If 8<D<12 then 5xD
If D>12 then 6xD
Flame propagition test on single cable
EN 60332-1
AC test voltage
Rated voltage Uo/U
ROHS & REACH compliant
Lead free
APPLICATIONS
Used in underground which there not much outer factors and inside cable conduits.
TECHNICAL DATA ( Cu/PVC/PVC )
Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in | |
---|---|---|---|---|---|
Ground (A) | Air (A) | ||||
YVV-U (NYY), YVV-R (NYY) (0.6/1 kV)
|
|||||
4x1.5 | 12.00 | 222 | 12.1 | 27 | 18.5 |
4x2.5 | 13.00 | 280 | 7.41 | 36 | 25 |
4x4 | 15.00 | 398 | 4.61 | 47 | 34 |
4x6 | 16.20 | 500 | 3.08 | 59 | 43 |
4x10 | 19.00 | 734 | 1.83 | 79 | 60 |
4x16 | 21.50 | 1026 | 1.15 | 102 | 80 |
4x25 | 24.90 | 1490 | 0.727 | 133 | 101 |
4x35 | 27.60 | 1947 | 0.524 | 159 | 126 |
4x50 | 31.90 | 2621 | 0.387 | 188 | 153 |
4x70 | 35.90 | 3586 | 0.268 | 232 | 199 |
4x95 | 41.20 | 4841 | 0.193 | 280 | 246 |
4x120 | 45.50 | 6004 | 0.153 | 318 | 285 |