Skip links

YXV (N2XY) (0,6/1 kV)

YXV 3

XLPE Insulated, Multi-core Cables With Copper Conductor

TS IEC 60502-1

CONSTRUCTION

Conductor

Örgülü bakır
Solid or stranded copper (Class 1 or Class 2)

Insulation

XLPE
Cross linkable polyethylene

Outer Sheath

PVC
Polyvinyl chloride

Outer Sheath

PVC 4
Polyvinyl chloride

SPECIFICATIONS

250 derece
Max. short circuit temperature
90 derece
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları

This cable having very low dilectric loss is used indoor, in cable ducts and in industrial plants or switching stations where mechanical damage is not anticipated. Suitable for comparatively high ambient temperature due to high maximum permissible conductor temperature.

TECHNICAL DATA ( CU/XLPE/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YXV (N2XY) (0.6/1 kV)
3x16/10 19.8 858 1.15/1.83 112 98
3x25/16 23.0 1247 0.727/1.15 145 133
3x35/16 25.4 1574 0.524/1.15 174 162
3x50/25 28.9 2117 0.387/0.727 206 197
3x70/35 32.8 2912 0.268/0.524 254 250
3x95/50 37.2 3909 0.193/0.387 305 308
3x120/70 42.0 5018 0.153/0.268 348 359
4x1.5 11.1 186 12.1 31 24
4x2.5 12.0 236 7.41 40 32
4x4 13.1 316 4.61 52 42
4x6 14.6 422 3.08 64 53
4x10 17.4 639 1.83 86 74
4x16 19.7 906 1.15 112 98
4x25 23.0 1333 0.727 145 133
4x35 26.1 1799 0.524 174 162
4x50 29.9 2404 0.387 206 197
4x70 34.4 3374 0.268 254 250
4x95 38.8 4509 0.193 305 308
4x120 44.2 5748 0.153 348 359