YXV (N2XY) (0,6/1 kV)

YXV 2

PVC Insulated, Low Voltage Power Cables

TS IEC 60502-1

CONSTRUCTION

Conductor

Örgülü bakır
Solid or stranded copper (Class 1 or Class 2)

Insulation

XLPE
Cross linkable polyethylene

Outer Sheath

PVC
Polyvinyl chloride

Outer Sheath

PVC 4
Polyvinyl chloride

SPECIFICATIONS

250 derece
Max. short circuit temperature
90 derece
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları

This cable having very low dilectric loss is used indoor, in cable ducts and in industrial plants or switching stations where mechanical damage is not anticipated. Suitable for comparatively high ambient temperature due to high maximum permissible conductor temperature.

TECHNICAL DATA ( CU/XLPE/PVC/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YXV (N2XY) (0.6/1 kV)
2x1.5 10.14 145 12.1 37 26
2x2.5 10.92 179 7.41 49 36
2x4 11.82 227 4.61 64 49
2x6 12.82 285 3.08 79 63
2x10 15.10 420 1.83 106 86
2x16 17.2 587 1.15 137 115
2x25 20.0 847 0.727 176 149
2x35 22.2 1102 0.524 213 185
2x50 25.4 1469 0.387 252 225
3x1.5 9.80 143 12.1 31 24
3x2.5 10.80 187 7.41 40 32
3x4 12.1 259 4.61 52 42
3x6 13.5 345 3.08 64 53
3x10 16.2 525 1.83 86 74
3x16 18.2 732 1.15 112 98
3x25 21.3 1075 0.727 145 133
3x35 23.6 1409 0.524 174 162
3x50 26.9 1874 0.387 206 197
3x70 31.0 2629 0.268 254 250
3x95 34.8 3491 0.193 305 308
3x120 39.2 4407 0.153 348 359
3x150 42.7 5368 0.124 392 412