YXV (N2XY) (0,6/1 kV)

YXV

PVC Insulated, Low Voltage Power Cables

TS IEC 60502-1

CONSTRUCTION

Conductor

Som veya örgülü bakır
Fine-stranded copper (Class 5)

Insulation

XLPE
Cross linkable polyethylene

Outer Sheath

PVC
Polyvinyl chloride

SPECIFICATIONS

250 derece
Max. short circuit temperature
90 derece
Max. operating temperature
Min. bükülme yarı çapı
Min. bending radius
If D<8 then 4xD
If 8<D<12 then 5xD
If D>12 then 6xD
Tek kablo düşey alev yayılma testi
Flame propagition test on single cable
EN 60332-1
3,5 kv
AC test voltage
06/1 kv
Rated voltage Uo/U
ROHS & REACH compliant
Lead free

APPLICATIONS

Uygulama alanları
Uygulama alanları

This cable having very low dilectric loss is used indoor, in cable ducts and in industrial plants or switching stations where mechanical damage is not anticipated. Suitable for comparatively high ambient temperature due to high maximum permissible conductor temperature.

TECHNICAL DATA ( CU/XLPE/PVC )

Nominal Cross Section mm² Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Ground (A) Air (A)
YXV (N2XY) (0,6/1 kV)
1x4 6,7 77 4,61 66 54 54 40
1x6 7,2 98 3,08 82 67 67 53
1x10 8,5 141 1,83 109 89 89 74
1x16 9,0 200 1,15 139 115 115 101
1x25 10,4 294 0,727 179 148 148 135
1x35 11,5 389 0,524 213 177 177 169
1x50 13,0 515 0,387 251 209 209 207
1x70 14,7 720 0,268 307 256 256 268
1x95 16,6 970 0,193 366 307 307 328
1x120 18,5 1214 0,153 416 349 349 383
1x150 20,2 1488 0,124 465 393 393 444